Overfill Protection&Earthing System is on display at the Argentina exhibition
The ATEX approved “Overfill Protection and Earthing Systems” are
designed for bottom loading of tank trucks, rail cars, etc. In the event of an
overfill condition, the overfill sensor will send a signal through the output
relay to the terminal automated loading system to shut down the loading
operation. The systems provide overfill protection as well as grounding
verification.
Specifications:
Input Power: 85VAC to 250VAC 50Hz
Input current: <60mA
Alarm Type: Visible alarm
Spiral cable: Extendable to 8m (26ft.)
Output Safety Parameters:
Um:250VAC,Uo:21.42VDC,Io:149mA,Po:798mW,Co:1.19μF,
Lo:6.4mH (for overfill sensor )
Um:250VAC,Uo:14.28VDC,Io:96.2mA,Po:343mW,Co:4.28μF,
Lo:15.4mH (for earthing senor)
Operation Temperature: -20℃ to +55℃ (-4℉ to +131℉)
EU-Type Examination Certificate No.: Presafe 16 ATEX
8909X
QAN Certificate No.: Presafe 16 ATEX 7744Q
Applicable Directive: 2014/34/EU
Features & Benefits
◆ Designed and produced according to API standards.
◆ Compatible with overfill sensors and sockets that meet API standard.
◆ Monitors up to 6 overfill sensors.